"Values of Variables" view is showing time for "Last Refresh" in Red.

The Values of Variables view does show values for variables but the time of the last refresh is represented in bold and red.

Cause: The application has been changed since it has been loaded onto the PLC. This is indicated by the different fingerprints within the Instance view.

Solution: Load the programming onto the PLC. Subsequently, the fingerprint under Code-Identification is updated. Make sure that the execution of the programming has been started on the PLC.