Can the loading of the application onto the PLC be time-limited?

Yes.
If the loading of the application onto the PLC has not been finished within of 20 seconds, logi.CAD 3 reports a timeout. If you want to define a smaller or larger time period, define a different timeout:

  1. Go to the folder where you installed logi.CAD 3.

  2. Locate the file logiCAD3.ini and open it in a text editor.

  3. Enter -DUploadTimeout with a value in milliseconds after the option -vmargs.

    Example
    ...
    -vmargs
    -Dosgi.requiredJavaVersion=1.8
    -Xms256m
    -Xmx6144m
    -DUploadTimeout=30000

    The value 30000 corresponds to 30 seconds.

  4. Save the file.

  5. Start logi.CAD 3 and load the application onto the PLC.
    If it is not possible to load the application within the defined time period (hence within the defined 10 seconds), this message is displayed: Timeout while executing target command "ACTIVATE" (IP address of target is IP address)

images/s/b2ic8e/9012/1ca6q62/_/images/icons/emoticons/information.svg logi.cals recommends to install and use the most current versions of logi.CAD 3 and the runtime system so that the latest features and problem fixes according to the release notes are provided in the used version.