TO_BCD_WORD block

Short summary

Name

TO_BCD_WORD

→POU type

→function

Category

IEC-block, Convert

Conform to →IEC-standard

images/s/b2ic8e/9012/1ca6q62/_/images/icons/emoticons/check.svg no restrictions

Graphical interface

images/download/thumbnails/414781068/TO_BCD_WORD-version-1-modificationdate-1534929630513-api-v2.png

Available since

version 1.22.0 (for logi.CAD 3)

Functionality

The block converts a decimal value into a binary coded decimal value (a →BCD-value) .

At input IN, connect the decimal value that should be converted. If the decimal value has more than 4 digits, only the 4 rightmost digits are considered. The remaining digits are not accepted by the data type of the return value. In case of decimal values < 0, the block always returns value 0.

Inputs, return value


Identifier

→Data type

Description

Inputs:

IN

USINT, UINT, UDINT, ULINT, SINT, INT, DINT or LINT(corresponds to →generic data type ANY_INT)

decimal input value

Return value:

WORD


Input EN and output ENO are available when →calling the block. See "Execution control: EN, ENO" for information on input EN and output ENO.

Example for usage within ST-editor

PROGRAM Test
VAR
result1, result2 : WORD;
END_VAR
result1 := TO_BCD_WORD(IN := 4_321); (* The variable 'result' evaluates to '16#4321' (decimal: 17_185). *)
result2 := TO_BCD_WORD(IN := 32_767); (* The variable 'result' evaluates to '16#2767' (decimal: 10_087). *)
(* Note: The single underscore character '_' has been inserted as separator to make the decimal values in the sample more readable. *)
END_PROGRAM

When creating your application within the ST-editor, enter a call of a block by typing the text as requested by the syntax or use Content Assist.